Scald risk in social housing can be reduced through thermostatic control system without increasing Legionella risk: a cluster randomised trial.


Edwards, P; Durand, MA; Hollister, M; Green, J; Lutchmun, S; Kessel, A; Roberts, I; (2011) Scald risk in social housing can be reduced through thermostatic control system without increasing Legionella risk: a cluster randomised trial. Archives of disease in childhood, 96 (12). pp. 1097-102. ISSN 0003-9888 DOI: https://doi.org/10.1136/archdischild-2011-300606

[img]
Preview
Text - Accepted Version
License:

Download (228kB) | Preview

Abstract

OBJECTIVE: To quantify the effects of a thermostatic control system in social (public) housing on the prevalence of dangerous (>60°C) water temperatures and on fuel consumption.<br/> DESIGN: Pair-matched double-blind cluster randomised controlled trial.<br/> SETTING: Social housing in a deprived inner-London borough.<br/> PARTICIPANTS: 150 households recruited as clusters from 22 social housing estates. Four small estates were combined into two clusters (resulting in a total of 10 pairs of clusters).<br/> INTERVENTION: Social housing estate boiler houses were randomised to a thermostatic control sterilisation programme (heating water to 65°C during 00:00-06:00 h and to 50°C from 06:00 to 00:00 h daily) or to standard control (constant temperature 65°C).<br/> MAIN OUTCOME MEASURES: Water temperature over 60°C ('dangerous') after running taps for 1 min and daily fuel consumption (cubic feet of gas).<br/> RESULTS: 10 clusters (80 households) were allocated to the sterilisation programme and 10 clusters (70 households) to control, of which 73 and 67 households, respectively, were analysed. Prevalence of dangerous (>60°C) hot water temperatures at 1 min was significantly reduced with the sterilisation programme (mean of cluster prevalence 1% in sterilisation programme group vs 34% in control group; absolute difference 33%, 95% CI 12% to 54%; p=0.006). Prevalence of high (>55°C) hot water temperatures at 1 min was significantly reduced (31% sterilisation vs 59% control; absolute difference 28%, 95% CI 9% to 47%; p=0.009). Gas consumption per day reduced more in the control group than in the sterilisation programme group, although not statistically significantly (p=0.125).<br/> CONCLUSIONS: The thermostatic control with daily sterilisation was effective in capping hot water temperatures and therefore reduced scald risk. Although expected to save energy, fuel consumption was increased relative to the control group. Trial registration ClinicalTrials.gov ID: NCT00874692.<br/>

Item Type: Article
Faculty and Department: Faculty of Public Health and Policy > Dept of Health Services Research and Policy
Faculty of Epidemiology and Population Health > Dept of Population Health (2012- ) > Dept of Nutrition and Public Health Interventions Research (2003-2012)
Faculty of Epidemiology and Population Health > Dept of Population Health (2012- )
Faculty of Public Health and Policy > Dept of Social and Environmental Health Research
Research Centre: Centre for Global Non-Communicable Diseases (NCDs)
PubMed ID: 21937486
Web of Science ID: 296923000002
URI: http://researchonline.lshtm.ac.uk/id/eprint/64

Statistics


Download activity - last 12 months
Downloads since deposit
291Downloads
417Hits
Accesses by country - last 12 months
Accesses by referrer - last 12 months
Impact and interest
Additional statistics for this record are available via IRStats2

Actions (login required)

Edit Item Edit Item